2.01 ACCEPTABLE MANUFACTURERA. Provide rolling fire doors by Overhead Door Corporation, Dallas, Texas; Telephone 800-887-3667 or
972-233-6611; Fax 972-233-0367.
2.02 ROLLING DOORS
A. Trade Reference: Series 630 Fire Doors by Overhead Door Corporation.
B. Label: Provide fire doors certified with the following listing.
1. Rolling fire doors
up to 144 sq. ft. and 12 in width or height shall bear the (UL and FM 3-Hour Class A Label.) (ULC 3-Hour Label.) (UL and FM 1-1/2 Hour Class B Label for non-masonry fire walls.)
2. Rolling fire doors over 144
sq. ft. shall receive the UL Oversize Fire Door Label.
3. Rolling fire doors over 144 sq. ft. and not exceeding 18 in height or width shall receive the Factory Mutual Label for Oversize Fire Doors.
C. Curtain:
Interlocking roll-formed slats as specified following. Endlocks shall be attached to each end of alternate slats to prevent lateral movement.
1. Curved profile type C-187 for doors thru 140 wide by 120 high,
fabricated of 22 gauge galvanized steel. (20 gauge galvanized steel.) (22 gauge stainless steel.)
2. Curved profile type C-187 for doors over 140 thru 200 wide, fabricated of 20 gauge galvanized steel. (18 gauge
galvanized steel.) (20 gauge stainless steel.)
3. Curved profile type C-275 for doors thru 140 wide by 120 high, fabricated of 22 gauge galvanized steel. (20 gauge galvanized steel.) (22 gauge stainless steel.)
4.
Curved profile type C-275 for doors over 140 thru 200 wide, fabricated of 20 gauge galvanized steel. (18 gauge galvanized steel.) (20 gauge stainless steel.)
5. Curved profile type C-275 for doors over 200 thru
240 wide, fabricated of 18 gauge galvanized steel. (16 gauge galvanized steel.)
6. Flat profile type F-265 for doors thru 140 wide by 120 high, fabricated of 22 gauge galvanized steel. (20 gauge galvanized steel.) (22
gauge stainless steel.)
7. Flat profile type F-265 for doors over 140 thru 200 wide, fabricated of 20 gauge galvanized steel. (18 gauge galvanized steel.) (20 gauge stainless steel.)
8. Flat profile type F-265 for
doors over 200 thru 240 wide, fabricated of 18 gauge galvanized steel.
D. Glazing: Not Required. (Fire-rated vision panels, four glazing panels 3 by 5/8; FireLite glazing as manufactured by Nippon Electric Glass Co.
and distributed by Technical Glass Products.)
E. Finish:
1. Galvanized Steel: Slats and hood shall be galvanized steel in accordance with ASTM A 525 and receive rust-inhibitive, roll coating process, including
bonderizing, 0.2 mils thick baked-on prime paint, and 0.6 mils thick baked-on polyester (powder coated) top coat. Non-galvanized exposed ferrous surfaces shall receive one coat of rust-inhibitive primer.
2. Stainless
Steel: Slats shall be stainless steel with (2B mill finish) (No. 4 satin finish).
F. Color: Gray polyester top coat. (Tan polyester top coat.) (Powder coating finish in color as selected by Architect from
manufacturers standard colors.)
G. Bottom Bar: Two (galvanized) structural steel angles 1-1/2 by 1-1/2 by 1/8 minimum. (Single angle for conveyor applications.) (Tubular locking bottom bar.) (Stainless steel.)
H.
Guides: Roll-formed steel shapes attached to continuous steel wall angle for doors thru 120 wide. Three structural steel angles with minimum thickness of 3/16 for doors over 12 wide. Guides for between jamb doors shall
be structural angles.
1. Fastening Guides to Masonry Fire Walls: UL listed expansion anchors, or by through-bolts on soft brick or hollow block walls, or by bolts on steel jambs, or welded in accordance with
manufacturers listing.
2. Fastening Guides to Non-Masonry Fire Walls: Comply with the manufacturers listing.
I. Brackets: Steel plate to support counterbalance, curtain and hood.
J. Counterbalance: Helical
torsion spring type. Counterbalance shall be housed in a steel tube or pipe barrel, supporting the curtain with deflection limited to 0.03 per foot of span. Counterbalance shall be adjustable by means of an
adjusting tension wheel.
K. Hood: 24 gauge galvanized primed steel minimum for wall openings thru 19 wide. 22 gauge galvanized primed steel for wall openings over 19 wide. Hood shall be equipped with thermally
controlled, internal, galvanized steel flame baffle as required. Provide one intermediate support bracket for wall openings over 136 wide and two support brackets for wall openings over 190 wide.
L. Manual Operation: Manual push up (Chain hoist.) (Crank.)
M. Electric Motor Operation: Provide UL listed electric operator, size as recommended by manufacturer to move door in either direction at not less than
2/3 foot nor more than 1 foot per second.
1. Sensing Edge Protection: (Pneumatic sensing edge.) (Electric sensing edge.)
2. Operator Controls: Push-button (Key) (Push-button and key) operated control stations with
open, close, and stop buttons for surface (flush) mounting, for interior (exterior) (both interior and exterior) location.
3. Special Operation: (Vehicle detector operation, radio control operation, card reader
control, photocell operation, door timer operation, commercial light package, explosion and dust ignition proof control wiring.)
N. Automatic Closure: Provide automatic closure thermally controlled by means of 165
degree fusible links. Operating mechanism shall be disengagedduring automatic closing. Automatic closing rate shall be controlled by a governor.
1. Time Delay Release Device: UL 864 rated; Fire Sentinel. (Provide
UL/FM fail safe release device, Model A or B.) (Provide UL/FM fail safe release device with internal battery, Model B2.) (Provide UL/FM fail safe release device with internal battery to close fire door on alarm by
electric operation with commercial power; Model C.)
2. Provide automatic closing on alarm by electric operator with uninterruptible power supply for operator.
O. Locking: (Interior bottom bar slide bolt.) (Interior
slide lock for electric operation with interlock switch.) (Cylinder locking bottom bar with mortise cylinders.)
P. Wall Mounting Condition: Face-of-wall mounting. (Between jambs mounting.)
PART 3 -